Sample Report
1847 S. Magnolia Avenue, Tampa, FL 33629
⚠ Sample Report
1847 S. Magnolia Avenue
Tampa, FL 33629 — Hyde Park
Scan Date: May 9, 2026
Method: UplinkRobotics Wombat · 4K high-definition video
Services: Complete PierScan — Crawl Space & Attic
Zones: 11 zones — 8 crawl space, 3 attic
Report: PierScan.io
Contact: (813) 705-4590
Full Report
Zone Map
Summary
Video
Legend
▼ Crawl Space Documentation
Zone 1 Access Point
Ground Surface Soil dry, no visible moisture. Zone 1
Photo 1
Zone 1 — Ground surface
Soil dry, no visible moisture observed at access point. Ground surface visible, no standing water or saturation.
Consult a licensed professional for evaluation.
Pier & Beam Sistered joist observed — evidence of prior repair. Zone 1, north perimeter beam. Zone 1
Photo 2
Zone 1 — Sistered joist
Photo 3
Zone 1 — Beam detail
Sistered joist observed in Zone 1, north perimeter beam. New lumber observed attached alongside existing member. Evidence of prior repair. See photo.
Consult a licensed professional for evaluation.
Zone 2 North Foundation
Biological Columnar biological structures (mud-like material) observed on beam face. Zone 2, approx 14 inches in length. See photo 4. Zone 2
Photo 4
Zone 2 — Biological indicator
Photo 5 (close)
Zone 2 — Detail with arrow
Columnar biological structures (mud-like material) observed on beam face in Zone 2. Length approximately 14 inches. Type undetermined. See photo 4 and 5. Arrow annotation indicates location on beam surface.
Consult a licensed professional for evaluation.
Plumbing Mineral deposits / staining observed on pipe surface, Zone 2. Zone 2
Photo 6
Zone 2 — Pipe staining
Mineral deposit accumulation and surface discoloration observed on pipe surface in Zone 2. See photo. Visual observation only.
Consult a licensed professional for evaluation.
Ground Surface Soil damp to visual observation. No standing water. Zone 2, NW corner. Zone 2
Photo 7
Zone 2 — Soil moisture
Soil damp to visual observation in Zone 2, NW corner. No standing water observed. Darker soil coloration consistent with elevated moisture content. Area approximately 3ft × 2ft.
Consult a licensed professional for evaluation.
Zone 3 East Foundation
Insulation & Vapor Barrier Vapor barrier observed torn and displaced in Zone 3, NE quadrant. Zone 3
Photo
Zone 3 — Vapor barrier torn / displaced
Vapor barrier observed torn and displaced in Zone 3, NE quadrant. Affected area approximately 4ft x 3ft. Adjacent vapor barrier intact.
Consult a licensed professional for evaluation.
Pier & Beam Wood member shows visible surface deterioration (flaking, softening). Zone 3, east perimeter joist. Zone 3
Photo 8
Zone 3 — Surface deterioration
Wood member shows visible surface deterioration (flaking, softening) in Zone 3, east perimeter joist. Approximately 24 inches of affected surface visible. See photo. Visual observation only.
Consult a licensed professional for evaluation.
Electrical Wiring with aged cloth/rubber insulation observed in Zone 3. Visible insulation deterioration noted. Visual observation only, not tested. Zone 3
Photo 9
Zone 3 — Wiring
Wiring with aged cloth/rubber insulation observed in Zone 3. Visible insulation deterioration (cracking/flaking) noted on wiring surface. Visual observation only — not tested, not evaluated.
Consult a licensed professional for evaluation.
Zone 4 South Foundation
Plumbing Moisture present on exterior surface of pipe at Zone 4, beneath bathroom subfloor area, near joint. Zone 4
Photo
Zone 4 — Pipe exterior moisture
Moisture present on exterior surface of pipe at Zone 4, beneath bathroom subfloor area, near joint. See photo. Visual observation only.
Consult a licensed professional for evaluation.
Pier & Beam Gap visible between pier top and beam in Zone 4. No measurement taken. Zone 4
Photo 10
Zone 4 — Pier gap
Gap visible between pier top and beam in Zone 4. No measurement taken. See photo.
Consult a licensed professional for evaluation.
Zone 5 Center Run
Access Limitation Robot access not possible in Zone 5, NW section due to insufficient vertical clearance. Zone 5
Robot access not possible in Zone 5, NW section due to insufficient vertical clearance. Area approximately 6ft × 4ft undocumented. All accessible areas of Zone 5 center run documented. This limitation is noted on the zone map.
Consult a licensed professional for evaluation if this area is of concern.
▼ Attic Documentation
Attic Zone A1 — Access Point
Access & Entry Attic access panel observed at [location]. Entry area clear at time of scan. Attic A1
Photo A1
Attic A1 — Access panel
Attic access panel observed at [location]. Entry area clear at time of scan.
Consult a licensed professional for evaluation.
Attic Zone A2 — North Section
Roof Deck & Framing Surface discoloration observed on roof decking in Zone A2. Type undetermined. Attic A2
Photo A2
Attic A2 — Roof decking
Surface discoloration observed on roof decking in Zone A2. Type undetermined. See photo.
Consult a licensed professional for evaluation.
Attic Zone A3 — East Section
Insulation Insulation material observed compressed / displaced in Zone A3. Attic A3
Photo A3
Attic A3 — Insulation
Insulation material observed compressed / displaced in Zone A3. See photo.
Consult a licensed professional for evaluation.
Attic Zone A4 — South Section
Electrical Wiring with ceramic insulator-style hardware and cloth-wrapped conductors observed. Visual observation only, not tested. Attic A4
Photo A4
Attic A4 — Wiring
Wiring with ceramic insulator-style hardware and cloth-wrapped conductors observed on framing members in Zone A4. Visual observation only, not tested. See photo.
Consult a licensed electrician for evaluation.
Attic Zone A5 — Center
Biological Indicators Granular debris and nesting-type material observed on attic floor in Zone A5. Type undetermined. Attic A5
Photo A5
Attic A5 — Biological material
Granular debris and nesting-type material observed on attic floor in Zone A5. Type undetermined. See photo.
Consult a licensed professional for evaluation.
Access Limitation Robot access not possible in Zone A5, NW section due to insulation depth. Attic A5
Robot access not possible in Zone A5, NW section due to insulation depth. Area undocumented. This limitation is noted on the attic zone map.
Consult a licensed professional for evaluation if this area is of concern.
Foundation Zone Map — 1847 S. Magnolia Avenue
ZONE 1 Access Point ZONE 2 N. Foundation ZONE 3 E. Foundation ZONE 4 S. Foundation ZONE 5 Center Run B T1 T2 IN Limited Biological indicator moisture observation Pier gap
1
Access Point
2 observations
2
North Foundation
3 observations · 1 biological
3
East Foundation
3 observations · 1
4
South Foundation
2 observations · 1
5
Center Run
1 access limitation
Attic Zone Map — 1847 S. Magnolia Avenue
ZONE A1 Access Point ZONE A2 N. Section ZONE A3 E. Section ZONE A4 S. Section ZONE A5 Center IN D B E Limited Biological indicator Electrical observation Staining / discoloration
A1
Access Point
1 observation
A2
North Section
1 observation · decking discoloration
A3
East Section
1 observation · insulation
A4
South Section
1 observation · electrical
A5
Center
1 biological · 1 access limitation
Summary of Observations — 1847 S. Magnolia Avenue, Tampa, FL 33629 33629
Scan date: May 9, 2026. Method: UplinkRobotics Wombat · 4K high-definition video. All observations recorded using approved neutral documentation language. This summary does not interpret, diagnose, or recommend repair.
Pier, Beam & Joists
Zone 1
Sistered joist observed — evidence of prior repair. North perimeter beam.
Pier, Beam & Joists
Zone 3
Wood member shows visible surface deterioration (flaking, softening). East perimeter joist.
Pier, Beam & Joists
Zone 4
Gap visible between pier top and beam. No measurement taken.
Pier, Beam & Joists
Biological Indicators
Zone 2
Columnar biological structures (mud-like material) observed on beam face. Length approx 14 inches. See photo 4.
Biological Indicator
Insulation & Vapor Barrier
Zone 3
Vapor barrier observed torn and displaced. NE quadrant.
Insulation & Vapor Barrier
Zone 4
Moisture present on exterior surface of pipe at Zone 4, beneath bathroom subfloor area, near joint.
Plumbing & Electrical
Ground Surface & Drainage
Zone 1
Soil dry, no visible moisture.
Ground Surface
Zone 2
Soil damp to visual observation. No standing water. NW corner.
Ground Surface
Plumbing & Electrical
Zone 2
Mineral deposits / staining observed on pipe surface.
Plumbing
Zone 3
Non-metallic sheathed wiring visible, appears aged. Visual observation only, not tested.
Electrical
Access Limitations — Crawl Space
Zone 5
Robot access not possible in Zone 5, NW section due to insufficient vertical clearance. Area approximately 6ft × 4ft undocumented.
Access Limitation
Attic — Roof Deck & Framing
Attic A2
Surface discoloration observed on roof decking. Type undetermined. See photo A2.
Roof Deck & Framing
Attic — Insulation
Attic A3
Insulation material observed compressed / displaced. See photo A3.
Insulation
Attic — Electrical
Attic A4
Wiring with ceramic insulator-style hardware and cloth-wrapped conductors observed on framing members. Visual observation only, not tested. See photo A4.
Electrical
Attic — Biological Indicators
Attic A5
Granular debris and nesting-type material observed on attic floor. Type undetermined. See photo A5.
Biological Indicators
Attic — Access Limitations
Attic A5
Robot access not possible in Zone A5, NW section due to insulation depth. Area undocumented.
Access Limitation
Video Documentation
24:38
Full Video
Complete footage of the entire crawl. All zones.
Full raw video available on request. Contact PierScan at PierScan.io or (813) 705-4590.
Plain-Language Legend

PierScan reports use neutral documentation language only. This legend translates the terms used in your report into plain English and indicates what next steps typically look like for each finding type.

Columnar biological structures (mud-like material)
A tube-like structure made of a mud-like material, found on a wood member or masonry surface. The robot documented what it saw. Type and origin are not determined by this report.
Consult a licensed professional for evaluation.
Wood member shows visible surface deterioration (flaking, softening)
The outer surface of a wood beam or joist shows visible surface deterioration — flaking or softening. The robot documented the visual condition only.
Consult a licensed professional for evaluation.
Gap visible between pier top and beam
A space was observed between the top of a brick or concrete pier and the beam it is meant to support. This was documented visually. No measurement was taken.
Consult a licensed professional for evaluation.
Mineral deposits / staining on pipe surface
White or discolored deposits, or staining, on the outside of a pipe. This is a visual observation only. Source and cause are not determined by this report.
Consult a licensed professional for evaluation.
Sistered joist — evidence of prior repair
A second piece of lumber has been attached alongside an existing beam or joist. This is a common repair technique. The documentation notes the observation — it does not evaluate the quality or adequacy of the repair.
Consult a licensed professional for evaluation.
Robot access not possible — insufficient clearance
The robot could not reach a specific area because there was not enough vertical space for it to pass through. That area is undocumented. This limitation is noted on the zone map.
Consult a licensed professional for evaluation.
Attic Observations
Surface discoloration observed on roof decking — type undetermined
A discolored area was observed on the underside of the roof decking. The robot documented what was visible. The type, source, and extent of the discoloration are not determined by this report.
Consult a licensed professional for evaluation.
Insulation material observed compressed / displaced
The insulation material in the attic was observed to be pressed down or shifted from its original position. The robot documented the visible condition only. No assessment of cause or thermal impact is made.
Consult a licensed professional for evaluation.
Wiring with ceramic insulator-style hardware and cloth-wrapped conductors observed
Wiring was observed that has ceramic knob-style insulators mounted to framing members and ceramic tube-style hardware where conductors pass through framing. The conductors are wrapped in cloth material. This is a visual observation only — the wiring was not tested and its condition is not evaluated by this report.
Consult a licensed electrician for evaluation.
Granular debris and nesting-type material — type undetermined
Material consistent in appearance with granular debris and nesting material was observed on the attic floor. The type and origin of the material are not determined by this report. The robot documented what was visible.
Consult a licensed professional for evaluation.
Robot access not possible — insulation depth
The robot could not reach a specific area of the attic because the insulation depth prevented passage. That area is undocumented. This limitation is noted on the attic zone map.
Consult a licensed professional for evaluation.